| Basic function | Position switches Safety position switches
 | 
		
			| Part group reference | LS(M)-… | 
		
			| Product range | Rounded plunger | 
		
			| Degree of Protection | IP66, IP67 | 
		
			| Features | Basic device, not expandable | 
		
			| Ambient temperature | -25 - +70 °C | 
		
			| N/C = Normally closed | 2 NC  | 
		
			| Notes |  = safety function, by positive opening to IEC/EN 60947-5-1 | 
		
			| Contact sequence |  | 
		
			| Contact travelâ–  = Contact closedâ–¡ = Contact open |  | 
		
			| Positive opening (ZW) | yes | 
		
			| Enclosure covers | Yellow | 
		
			| Enclosure covers |  | 
		
			| Housing | Insulated material | 
		
			| Connection type | Screw terminal | 
		
			| Standards | IEC/EN 60947 | 
		
			| Climatic proofing | Damp heat, constant, to IEC 60068-2-78; damp heat, cyclical, to IEC 60068-2-30 | 
		
			| Ambient temperature | -25 - +70 °C | 
		
			| Mounting position | As required | 
		
			| Degree of Protection | IP66, IP67 | 
		
			| Terminal capacities >Solid
 | 1 x (0.5 - 2.5) mm2 | 
		
			| Terminal capacities >Flexible with ferrule
 | 1 x (0.5 - 1.5) mm2 | 
		
			| Repetition accuracy | 0.15 mm | 
		
			| Rated impulse withstand voltage  [Uimp] | 4000 V AC | 
		
			| Rated insulation voltage [Ui
] | 400 V | 
		
			| Overvoltage category/pollution degree | III/3 | 
		
			| Rated operational current [Ie
	] >AC-15
 >24 V [Ie
	]
 | 6 A | 
		
			| Rated operational current [Ie
	] >AC-15
 >220 V 230 V 240 V [Ie]
 | 6 A | 
		
			| Rated operational current [Ie
	] >AC-15
 >380 V 400 V 415 V [Ie]
 | 4 A | 
		
			| Rated operational current [Ie
	] >DC-13
 >24 V [Ie
	]
 | 3 A | 
		
			| Rated operational current [Ie
	] >DC-13
 >110 V [Ie
	]
 | 0.6 A | 
		
			| Rated operational current [Ie
	] >DC-13
 >220 V [Ie
	]
 | 0.3 A | 
		
			| Control circuit reliability >at 24 V DC/5 mA [HF
	]
 | < 10 -7, < 1 fault in 107 operations Fault probability | 
		
			| Control circuit reliability >at 5 V DC/1 mA [HF
	]
 | < 5 x 10-6, < 1 failure at 5 x 106 operations Fault probability | 
		
			| Supply frequency | max. 400 Hz | 
		
			| Short-circuit rating to IEC/EN 60947-5-1 >max. fuse
 | 6 A gG/gL | 
		
			| Rated conditional short-circuit current | 1 kA | 
		
			| Lifespan, mechanical [Operations] | 8 x 106 | 
		
			| Contact temperature of roller head | ≦ 100 °C | 
		
			| Mechanical shock resistance (half-sinusoidal shock, 20 ms) >Standard-action contact
 | 25 g | 
		
			| Operating frequency [Operations/h] | ≦ 6000 | 
		
			| Mechanical >Actuating force at beginning/end of stroke
 | 1.0/8.0 N | 
		
			| Mechanical >Actuating torque of rotary drives
 | 0.2 Nm | 
		
			| Mechanical >Max. operating speed with DIN cam
 | 1/0.5 m/s | 
		
			| Mechanical >Notes
 | for angle of actuation α = 0°/30° | 
		
			| Rated operational current for specified heat dissipation [In] | 6 A | 
		
			| Heat dissipation per pole, current-dependent [Pvid] | 0.17 W | 
		
			| Equipment heat dissipation, current-dependent [Pvid] | 0 W | 
		
			| Static heat dissipation, non-current-dependent [Pvs] | 0 W | 
		
			| Heat dissipation capacity [Pdiss] | 0 W | 
		
			| Operating ambient temperature min. | -25 °C | 
		
			| Operating ambient temperature max. | +70 °C | 
		
			| 10.2 Strength of materials and parts >10.2.2 Corrosion resistance
 | Meets the product standard´s requirements. | 
		
			| 10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures
 | Meets the product standard´s requirements. | 
		
			| 10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat
 | Meets the product standard´s requirements. | 
		
			| 10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
 | Meets the product standard´s requirements. | 
		
			| 10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation
 | Meets the product standard´s requirements. | 
		
			| 10.2 Strength of materials and parts >10.2.5 Lifting
 | Does not apply, since the entire switchgear needs to be evaluated. | 
		
			| 10.2 Strength of materials and parts >10.2.6 Mechanical impact
 | Does not apply, since the entire switchgear needs to be evaluated. | 
		
			| 10.2 Strength of materials and parts >10.2.7 Inscriptions
 | Meets the product standard´s requirements. | 
		
			| 10.3 Degree of protection of ASSEMBLIES | Does not apply, since the entire switchgear needs to be evaluated. | 
		
			| 10.4 Clearances and creepage distances | Meets the product standard´s requirements. | 
		
			| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. | 
		
			| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. | 
		
			| 10.7 Internal electrical circuits and connections | Is the panel builder´s responsibility. | 
		
			| 10.8 Connections for external conductors | Is the panel builder´s responsibility. | 
		
			| 10.9 Insulation properties >10.9.2 Power-frequency electric strength
 | Is the panel builder´s responsibility. | 
		
			| 10.9 Insulation properties >10.9.3 Impulse withstand voltage
 | Is the panel builder´s responsibility. | 
		
			| 10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material
 | Is the panel builder´s responsibility. | 
		
			| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | 
		
			| 10.11 Short-circuit rating | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. | 
		
			| 10.12 Electromagnetic compatibility | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. | 
		
			| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. | 
		
			| Width sensor | 31 mm | 
		
			| Diameter sensor | 0 mm | 
		
			| Height of sensor | 61 mm | 
		
			| Length of sensor | 33.5 mm | 
		
			| Rated operation current Ie at AC-15, 24 V | 6 A | 
		
			| Rated operation current Ie at AC-15, 125 V | 6 A | 
		
			| Rated operation current Ie at AC-15, 230 V | 6 A | 
		
			| Rated operation current Ie at DC-13, 24 V | 3 A | 
		
			| Rated operation current Ie at DC-13, 125 V | 0.8 A | 
		
			| Rated operation current Ie at DC-13, 230 V | 0.3 A | 
		
			| Switching function | Slow-action switch | 
		
			| Switching function latching | No | 
		
			| Output electronic | No | 
		
			| Forced opening | Yes | 
		
			| Number of safety auxiliary contacts | 2 | 
		
			| Number of contacts as normally closed contact | 2 | 
		
			| Number of contacts as normally open contact | 0 | 
		
			| Number of contacts as change-over contact | 0 | 
		
			| Type of interface | None | 
		
			| Type of interface for safety communication | None | 
		
			| Construction type housing | Cuboid | 
		
			| Material housing | Plastic | 
		
			| Coating housing | Other | 
		
			| Type of control element | Plunger | 
		
			| Alignment of the control element | Other | 
		
			| Type of electric connection | Other | 
		
			| With status indication | No | 
		
			| Suitable for safety functions | Yes | 
		
			| Explosion safety category for gas | None | 
		
			| Explosion safety category for dust | None | 
		
			| Ambient temperature during operating | 25 - 70 °C | 
		
			| Degree of protection (IP) | IP67 | 
		
			| Degree of protection (NEMA) | 4X | 
		
			| Product Standards | IEC/EN 60947-5; UL 508; CSA-C22.2 No. 14; CE marking | 
		
			| UL File No. | E29184 | 
		
			| UL Category Control No. | NKCR | 
		
			| CSA File No. | 12528 | 
		
			| CSA Class No. | 3211-03 | 
		
			| North America Certification | UL listed, CSA certified | 
		
			| Degree of Protection | IEC: IP66, 67, UL/CSA Type 3R, 4X (indoor use only), 12, 13 |