Schmersal : TQ 700-20-101192481
TQ 700-20
TQ 700-20-101192481
1 Cable entry M 20 x 1.5Thermoplastic enclosureone-side operation / wire up to 10 m longPosition indicatorLarge wiring compartmentTwisting of towing eye not possibleOne tension force for cable lengths up to 10 m
- 1 Cable entry M 20 x 1.5
- Thermoplastic enclosure
- one-side operation / wire up to 10 m long
- Position indicator
- Large wiring compartment
- Twisting of towing eye not possible
- One tension force for cable lengths up to 10 m
Ordering data
Product type description | TQ 700-20 |
Article number (order number) | 101192481 |
EAN (European Article Number) | 4030661352695 |
eCl@ss number, version 12.0 | 27-27-06-07 |
eCl@ss number, version 11.0 | 27-27-06-07 |
eCl@ss number, version 9.0 | 27-27-06-07 |
ETIM number, version 7.0 | EC000030 |
ETIM number, version 6.0 | EC000030 |
Approvals - Standards
| cULus |
General data
Standards | EN IEC 60947-5-1 |
Housing material | Glass-fibre, thermoplastic |
Material of the housing cover | Glass-fibre, thermoplastic |
Length of the wire, maximum | 10 m |
Gross weight | 205 g |
General data - Features
Number of normally open (NO) | 2 |
Safety classification |
Standards | EN ISO 13849-1 |
Mission time | 20 Year(s) |
Safety classification - Safety outputs
B10D Normally open contact (NO) | 100,000 Operations |
Mechanical data
Mechanical life, minimum | 1,000,000 Operations |
Mechanical data - Connection technique
Termination | Screw terminals M20 x 1.5 |
Cable section, minimum | 0.75 mm² |
Cable section, maximum | 2.5 mm² |
Note | All indications including the conductor ferrules. |
Mechanical data - Dimensions
Width | 40.5 mm |
Height | 160 mm |
Depth | 42.2 mm |
Ambient conditions
Degree of protection | IP67 |
Ambient temperature | -25 ... +70 °C |
Ambient conditions - Insulation values
Rated insulation voltage Ui | 500 V |
Rated impulse withstand voltage Uimp | 6 kV |
Electrical data
Thermal test current | 10 A |
Utilisation category AC-15 | 230 VAC |
Utilisation category AC-15 | 4 A |
Utilisation category DC-13 | 24 VDC |
Utilisation category DC-13 | 4 A |
Switching element | Normally open contact (NO) |
Switching principle | Slow action |
Material of the contacts, electrical | Silver |
Note
Note (General) | Recommended cable lengths for pull-wire Emergency-Stop switches in relation to the range of ambient temperature. As the thimbles are subject to deformation in case of wire pull, the wire should be pulled several times after fitting. After that, the wire must be re-tensioned using the eyebolt or the tensioner. At 2 m ... 5 m distance intermediate wire supports are required, see accessories |
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.
Similar Products
Can't find the product you're looking for?
LET US HELP YOU
Can't Find the Product You're Looking For? Let Us Know, and We'll Source It for You!
Are you searching for products not listed on our website or out of stock? Let us know your requirements, and our expert team will contact you as soon as possible to find the most suitable solution for you.