| Basic function | DOL starters (complete devices) | 
		
			| Basic device | MSC | 
		
			| Notes | Not suitable for motors with efficiency class IE3. | 
		
			| Connection technique | Screw terminals | 
		
			| Connection to SmartWire-DT | no | 
		
			| Motor rating [P] >AC-3
 >380 V 400 V 415 V [P]
 |  | 
		
			| Rated operational current >AC-3
 >380 V 400 V 415 V [Ie]
 | 7.5 kW | 
		
			| Rated short-circuit current 380 - 415 V [Iq
	] | 15.2 A | 
		
			| Setting range of overload releases  [Ir] | 50 kA | 
		
			| Coordination |  | 
		
			| Contact sequence | 10 - 16 A | 
		
			| Actuating voltage | Type of coordination “1” | 
		
			| Motor-protective circuit-breakers |  | 
		
			| Contactor | 230 V 50 Hz, 240 V 60 Hz | 
		
			| DOL starter wiring set 
 Mechanical connection element and electrical electric contact module
 | AC | 
		
			| Notes | PKZM0-16 Type | 
		
			| Notes | DILM15-10(...) Part no. | 
		
			| Standards | PKZM0-XDM12 Type | 
		
			| Mounting position | BK25/3-PKZ0-E extension terminal and if necessary B3.../...-PKZ0 three-phase commoning link can be added to motor-starter combinations to make Type F starters in accordance with UL508. | 
		
			| Altitude | The DOL starters (complete units) consist of a PKZM0 motor protective circuit breaker and a DILM contactor. With the adapter-less top-hat rail mounting of starters up to 15 A, only the motor protective circuit breaker on the top-hat rail requires an adapter. The contactors are provided with mechanical support via a mechanical connection element. Control wire guide with max. 6 conductors up to 2.5 mm external diameter or 4 conductors up to 3.5 mm external diameter. The connection of the main circuit between PKZ and contactor is established with electrical contact modules. When using the auxiliary contacts DILA‐XHIT… (→ 101042) the plug-in electrical connector can be removed without the removal of the front mounting auxiliary contact. | 
		
			| Ambient temperature |  | 
		
			| Rated impulse withstand voltage  [Uimp] | IEC/EN 60947-4-1, VDE 0660 | 
		
			| Overvoltage category/pollution degree |  | 
		
			| Rated operational voltage [Ue] | Max. 2000 m | 
		
			| Rated operational current >Open, 3-pole: 50 – 60 Hz
 >380 V 400 V [Ie]
 | -25 - +55 | 
		
			| Motor protective circuit breaker PKZM0, PKE |  | 
		
			| DILM contactors >Current heat loss
 >Current heat loss at Ie to AC-3/400 V
 | 6000 V AC | 
		
			| DILM contactors >Power consumption of the coil in a cold state and 1.0 x US
 >Dual-voltage coil 50 Hz [Sealing]
 | III/3 | 
		
			| Auxiliary contacts >Pilot Duty
 >AC operated
 | 230 - 415 V | 
		
			| Auxiliary contacts >Pilot Duty
 >DC operated
 | 15 A | 
		
			| Auxiliary contacts >General Use
 >AC
 |  | 
		
			| Auxiliary contacts >General Use
 >AC
 | PKZM0 motor-protective circuit-breakers, see motor-protective circuit-breakers/PKZM0 product group DILM contactors, see contactor product group
 DILET timing relay, ETR, see contactors, electronic timing relays product group
 | 
		
			| Auxiliary contacts >General Use
 >DC
 | 10.5 W | 
		
			| Auxiliary contacts >General Use
 >DC
 | 1.4 W | 
		
			| Rated operational current for specified heat dissipation [In] |  | 
		
			| Heat dissipation per pole, current-dependent [Pvid] | A600 | 
		
			| Equipment heat dissipation, current-dependent [Pvid] | P300 | 
		
			| Static heat dissipation, non-current-dependent [Pvs] | 600  V | 
		
			| Heat dissipation capacity [Pdiss] | 15 A | 
		
			| Operating ambient temperature min. | 250  V | 
		
			| Operating ambient temperature max. | 1 A | 
		
			| 10.2 Strength of materials and parts >10.2.2 Corrosion resistance
 |  | 
		
			| 10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures
 | 15.5 A | 
		
			| 10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat
 | 3.5 W | 
		
			| 10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
 | 10.5 W | 
		
			| 10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation
 | 1.4 W | 
		
			| 10.2 Strength of materials and parts >10.2.5 Lifting
 | 0 W | 
		
			| 10.2 Strength of materials and parts >10.2.6 Mechanical impact
 | -25 °C | 
		
			| 10.2 Strength of materials and parts >10.2.7 Inscriptions
 | +55 °C | 
		
			| 10.3 Degree of protection of ASSEMBLIES |  | 
		
			| 10.4 Clearances and creepage distances | Meets the product standard´s requirements. | 
		
			| 10.5 Protection against electric shock | Meets the product standard´s requirements. | 
		
			| 10.6 Incorporation of switching devices and components | Meets the product standard´s requirements. | 
		
			| 10.7 Internal electrical circuits and connections | Meets the product standard´s requirements. | 
		
			| 10.8 Connections for external conductors | Meets the product standard´s requirements. | 
		
			| 10.9 Insulation properties >10.9.2 Power-frequency electric strength
 | Does not apply, since the entire switchgear needs to be evaluated. | 
		
			| 10.9 Insulation properties >10.9.3 Impulse withstand voltage
 | Does not apply, since the entire switchgear needs to be evaluated. | 
		
			| 10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material
 | Meets the product standard´s requirements. | 
		
			| 10.10 Temperature rise | Does not apply, since the entire switchgear needs to be evaluated. | 
		
			| 10.11 Short-circuit rating | Meets the product standard´s requirements. | 
		
			| 10.12 Electromagnetic compatibility | Does not apply, since the entire switchgear needs to be evaluated. | 
		
			| 10.13 Mechanical function | Does not apply, since the entire switchgear needs to be evaluated. | 
		
			| Kind of motor starter | Is the panel builder´s responsibility. | 
		
			| With short-circuit release | Is the panel builder´s responsibility. | 
		
			| Rated control supply voltage Us at AC 50HZ | Is the panel builder´s responsibility. | 
		
			| Rated control supply voltage Us at AC 60HZ | Is the panel builder´s responsibility. | 
		
			| Rated control supply voltage Us at DC | Is the panel builder´s responsibility. | 
		
			| Voltage type for actuating | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | 
		
			| Rated operation power at AC-3, 230 V, 3-phase | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. | 
		
			| Rated operation power at AC-3, 400 V | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. | 
		
			| Rated power, 460 V, 60 Hz, 3-phase | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. | 
		
			| Rated power, 575 V, 60 Hz, 3-phase |  | 
		
			| Rated operation current Ie |  | 
		
			| Rated operation current at AC-3, 400 V | Direct starter | 
		
			| Overload release current setting | Yes | 
		
			| Rated conditional short-circuit current, type 1, 480 Y/277 V | 230 - 230 V | 
		
			| Rated conditional short-circuit current, type 1, 600 Y/347 V | 0 - 0 V | 
		
			| Rated conditional short-circuit current, type 2, 230 V | 0 - 0 V | 
		
			| Rated conditional short-circuit current, type 2, 400 V | AC | 
		
			| Number of auxiliary contacts as normally open contact | 4 kW | 
		
			| Number of auxiliary contacts as normally closed contact | 7.5 kW | 
		
			| Ambient temperature, upper operating limit | 0 kW | 
		
			| Temperature compensated overload protection | 0 kW | 
		
			| Release class | 15.2 A | 
		
			| Type of electrical connection of main circuit | 15 A | 
		
			| Type of electrical connection for auxiliary- and control current circuit | 16 - 16 A | 
		
			| Rail mounting possible | 0 A | 
		
			| With transformer | 0 A | 
		
			| Number of command positions | 0 A | 
		
			| Suitable for emergency stop | 0 A | 
		
			| Coordination class according to IEC 60947-4-3 | 1 | 
		
			| Number of indicator lights | 0 | 
		
			| External reset possible | 60 °C | 
		
			| With fuse | Yes | 
		
			| Degree of protection (IP) | CLASS 10 A | 
		
			| Degree of protection (NEMA) | Screw connection | 
		
			| Supporting protocol for TCP/IP | Screw connection | 
		
			| Supporting protocol for PROFIBUS | Yes | 
		
			| Supporting protocol for CAN | No | 
		
			| Supporting protocol for INTERBUS | 0 | 
		
			| Supporting protocol for ASI | No | 
		
			| Supporting protocol for MODBUS | Class 1 | 
		
			| Supporting protocol for Data-Highway | 0 | 
		
			| Supporting protocol for DeviceNet | No | 
		
			| Supporting protocol for SUCONET | No | 
		
			| Supporting protocol for LON | IP20 | 
		
			| Supporting protocol for PROFINET IO | Other | 
		
			| Supporting protocol for PROFINET CBA | No | 
		
			| Supporting protocol for SERCOS | No | 
		
			| Supporting protocol for Foundation Fieldbus | No | 
		
			| Supporting protocol for EtherNet/IP | No | 
		
			| Supporting protocol for AS-Interface Safety at Work | No | 
		
			| Supporting protocol for DeviceNet Safety | No | 
		
			| Supporting protocol for INTERBUS-Safety | No | 
		
			| Supporting protocol for PROFIsafe | No | 
		
			| Supporting protocol for SafetyBUS p | No | 
		
			| Supporting protocol for other bus systems | No | 
		
			| Width | No | 
		
			| Height | No | 
		
			| Depth | No | 
		
			| Product Standards | No | 
		
			| UL File No. | No | 
		
			| UL Category Control No. | No | 
		
			| CSA File No. | No | 
		
			| CSA Class No. | No | 
		
			| North America Certification | No | 
		
			| Specially designed for North America | No |